File #: 2024-3789    Version: 1 Name:
Type: Consent Status: Passed
File created: 8/23/2024 In control: OPERATIONS COMMITTEE
On agenda: 11/6/2024 Final action: 11/6/2024
Title: DIGESTER K DOME REPAIR AT PLANT NO. 2, PROJECT NO. FR2-0032, SPECIFICATION NO. S-2024-630BD
Sponsors: Mike Dorman
Attachments: 1. Agenda Report, 2. Draft Services Contract - Structural Preservation Systems
Related files: 2024-3950
FROM: Robert Thompson, General Manager
Originator: Mike Dorman, Director of Engineering

SUBJECT:

title
DIGESTER K DOME REPAIR AT PLANT NO. 2, PROJECT NO. FR2-0032, SPECIFICATION NO. S-2024-630BD
end

GENERAL MANAGER'S RECOMMENDATION

recommendation
RECOMMENDATION: Recommend to the Board of Directors to:

A. Approve a Services Contract to Structural Preservation Systems for Digester K Dome Repair at Plant No. 2, Project No. FR2-0032, Specification No. S-2024-630BD, for a total amount not to exceed $876,707; and

B. Approve a contingency of $131,506 (15%).
body

BACKGROUND

Orange County Sanitation District (OC San) Digesters I, J, and K at Plant No. 2 are used as holding tanks for digested sludge prior to sludge dewatering by the downstream dewatering centrifuges.

Digester K, built in 1971, has been out of operation and empty since 2021 due to required structural repairs under this project.

RELEVANT STANDARDS

* Comply with California Public Contract Code Section 20103.8, award a contract to lowest responsive, responsible bidder text here
* Protect OC San assets
* 24/7/365 treatment plant reliability
* Commitment to safety & reducing risk in all operations

PROBLEM

The Digester K Dome cannot hold gas pressure due to multiple full penetration cracks on the dome surface. The concrete dome also lacks adequate rebar cover and concrete thickness in some locations, which was identified during the structural condition assessment. Multiple efforts to spot-repair the cracks have been attempted in the past but did not produce successful results. Repairs are required to bring Digester K back into service.

PROPOSED SOLUTION

Approve a Services Contract for Digester K Dome Repair at Plant No. 2, Project No. FR2-0032, Specification No. S-2024-630BD. The project will repair full penetration cracks and address previously repaired cracks that failed for the entire digester dome. Cracks will be repaired by injecting a crack resin designed to fill ...

Click here for full text