File #: 2020-1044    Version: 1 Name:
Type: Consent Status: Passed
File created: 4/16/2020 In control: OPERATIONS COMMITTEE
On agenda: 6/3/2020 Final action: 6/3/2020
Title: TOSHIBA 12KV CIRCUIT BREAKER PURCHASE
Sponsors: Rob Thompson
Attachments: 1. Agenda Report, 2. File Summary
Related files: 2020-1105
FROM: James D. Herberg, General Manager
Originator: Rob Thompson, Assistant General Manager

SUBJECT:

title
TOSHIBA 12KV CIRCUIT BREAKER PURCHASE
end

GENERAL MANAGER'S RECOMMENDATION

recommendation
RECOMMENDATION: Recommend to the Board of Directors to:

A. Award a Purchase Order Contract to Superior Electric Motor Services for the purchase of eight Toshiba HVK 12kV circuit breakers for Plant No. 1 Electrical Distribution System, per Specification No. E-2020-1162BD, for a total amount not to exceed $195,072, including sales tax and freight; and

B. Approve a contingency of $9,754 (5%).
body

BACKGROUND

The Orange County Sanitation District (Sanitation District) Plant No. 1 Power Building 5 12 kV circuit breakers are over 20 years old and have reached the end of their useful life. The Toshiba VK type 1 circuit breakers currently in service are obsolete and no longer supported nor repairable by Toshiba's field service repair shop. Replacement parts are also not available. Toshiba redesigned the circuit breakers and changed their designation to HVK. The Toshiba HVK circuit breakers are the only circuit breakers compatible with 12 kV switchgear in Power Building 5.

RELEVANT STANDARDS

* Protect Orange County Sanitation District assets
* Maintain a proactive asset management program
* Sustain 1, 5, 20-year planning horizons
* 24/7/365 treatment plant reliability

PROBLEM

Toshiba model VK circuit breakers have reached the end of their useful life. Preventive maintenance performed identified contact wear at their maximum allowable limit. Toshiba no longer supports repair services because parts are unavailable for these circuit breakers.


PROPOSED SOLUTION

Competitively bid and subsequently approve a purchase order to the lowest responsive and responsible bidder, for the purchase of eight new Toshiba HVK 12 kV circuit breakers for Plant No. 1 Power Building 5.

TIMING CONCERNS

The replacement of 12 kV circuit breakers are required fo...